Eaton
S611C180P3S
Reduced Voltage Motor Starter (RVMS) / Soft-starter (SS) for pump control - Eaton / Cutler-Hammer (S611) - Rated input voltage (3-phase (3P)) 130Vac-600Vac - Rated output current 180A (Standard duty) - Rated power 150HP (480V; Standard duty; 300% current for 15s; 115% continuous) - Frame size C - with Silicon Controlled Rectifiers (SCRs) + Internal bypass
Brand
SKU
S611C180P3S
Please add this item to cart to request a quote.
Eaton - S611S611C180P3S
Description
Reduced Voltage Motor Starter (RVMS) / Soft-starter (SS) for pump control - Eaton / Cutler-Hammer (S611) - Rated input voltage (3-phase (3P)) 130Vac-600Vac - Rated output current 180A (Standard duty) - Rated power 150HP (480V; Standard duty; 300% current for 15s; 115% continuous) - Frame size C - with Silicon Controlled Rectifiers (SCRs) + Internal bypass
Specifications
Primary brand
Eaton
Secondary brand
Cutler-Hammer
Main function
Soft starter
Product series / family name
S611
Network frequency
(input) 47-63 Hz
Functions
Reduced Voltage Motor Starter (RVMS) / Soft-starter (SS) for pump control
Supply voltage (AC)
130Vac-600Vac
Type of network
3-phase input (3P)
Rated current
180A (Standard duty; 300% current for 15s; 115% continuous)
180A (Standard duty plus; 350% FLA for 30s; 115% continuous)
117A (Severe duty; 600% FLA for 30s; 125% continuous)
180A (Standard duty plus; 350% FLA for 30s; 115% continuous)
117A (Severe duty; 600% FLA for 30s; 125% continuous)
Rated power (HP)
150HP (480V; Standard duty; 300% current for 15s; 115% continuous)
60HP (208V; Standard duty; 300% current for 15s; 115% continuous)
60HP (240V; Standard duty; 300% current for 15s; 115% continuous)
150HP (600V; Standard duty; 300% current for 15s; 115% continuous)
60HP (208V; Standard duty plus; 350% FLA for 30s; 115% continuous)
60HP (240V; Standard duty plus; 350% FLA for 30s; 115% continuous)
150HP (480V; Standard duty plus; 350% FLA for 30s; 115% continuous)
150HP (600V; Standard duty plus; 350% FLA for 30s; 115% continuous)
40HP (208V; Heavy duty; 500% FLA for 30s; 125% continuous)
60HP (240V; Heavy duty; 500% FLA for 30s; 125% continuous)
125HP (480V; Heavy duty; 500% FLA for 30s; 125% continuous)
150HP (600V; Heavy duty; 500% FLA for 30s; 125% continuous)
30HP (208V; Severe duty; 600% FLA for 30s; 125% continuous)
50HP (240V; Severe duty; 600% FLA for 30s; 125% continuous)
100HP (480V; Severe duty; 600% FLA for 30s; 125% continuous)
125HP (600V; Severe duty; 600% FLA for 30s; 125% continuous)
60HP (208V; Standard duty; 300% current for 15s; 115% continuous)
60HP (240V; Standard duty; 300% current for 15s; 115% continuous)
150HP (600V; Standard duty; 300% current for 15s; 115% continuous)
60HP (208V; Standard duty plus; 350% FLA for 30s; 115% continuous)
60HP (240V; Standard duty plus; 350% FLA for 30s; 115% continuous)
150HP (480V; Standard duty plus; 350% FLA for 30s; 115% continuous)
150HP (600V; Standard duty plus; 350% FLA for 30s; 115% continuous)
40HP (208V; Heavy duty; 500% FLA for 30s; 125% continuous)
60HP (240V; Heavy duty; 500% FLA for 30s; 125% continuous)
125HP (480V; Heavy duty; 500% FLA for 30s; 125% continuous)
150HP (600V; Heavy duty; 500% FLA for 30s; 125% continuous)
30HP (208V; Severe duty; 600% FLA for 30s; 125% continuous)
50HP (240V; Severe duty; 600% FLA for 30s; 125% continuous)
100HP (480V; Severe duty; 600% FLA for 30s; 125% continuous)
125HP (600V; Severe duty; 600% FLA for 30s; 125% continuous)
Net Height (mm)
529 mm
Net Width (mm)
294 mm
Net Depth (mm)
213 mm
Ambient air temperature for operation
-20...+50 °C
Ambient air temperature for storage
-40...+85 °C
Technology used in component
Silicon Controlled Rectifiers (SCRs)
Internal bypass
Internal bypass
Manufacturer product status
Commercialized
Compliant with standard(s)
IEC 60947-4-2
UL
CSA certified
UL
CSA certified
Benefits
The User Interface Module (UI) provides an intuitive; easy-to-use human interface with powerful configuration capabilities to maximize system performance
Door or device mounted UI enables users to safely configure; commission; monitor and troubleshoot the system at the electrical panel without opening the enclosure door; eliminating the possibility of an arc flash incident
System operating parameters can be monitored enterprise-wide through a communications network
Run bypass mode greatly reduces internal heating created by the greater power dissipation in the SCRs
Internal solid-state overload protection provides accurate current measurement and trip settings
Internal run bypass contactors and overload protection eliminate the need for additional devices
Wide range of overload FLA settings
Variable ramp times and torque control settings provide unlimited starting configurations
Kick-start feature enables soft starting of high friction loads
Soft stop control for applications where an abrupt stop of the load is not acceptable
Pump control option with sophisticated pump algorithms on both starting and stopping that minimize the pressure surges that cause water hammer
Soft acceleration and deceleration reduces wear on belts; gears; chains; clutches; shafts and bearings
Door or device mounted UI enables users to safely configure; commission; monitor and troubleshoot the system at the electrical panel without opening the enclosure door; eliminating the possibility of an arc flash incident
System operating parameters can be monitored enterprise-wide through a communications network
Run bypass mode greatly reduces internal heating created by the greater power dissipation in the SCRs
Internal solid-state overload protection provides accurate current measurement and trip settings
Internal run bypass contactors and overload protection eliminate the need for additional devices
Wide range of overload FLA settings
Variable ramp times and torque control settings provide unlimited starting configurations
Kick-start feature enables soft starting of high friction loads
Soft stop control for applications where an abrupt stop of the load is not acceptable
Pump control option with sophisticated pump algorithms on both starting and stopping that minimize the pressure surges that cause water hammer
Soft acceleration and deceleration reduces wear on belts; gears; chains; clutches; shafts and bearings
Net weight
15 kg
Degree of pollution
3