Eaton
LGS4250FAW
Molded/Moulded Case Circuit Breaker (MCCB) - Eaton (Series G) - LG-Frame) - 4 poles (4P3d) - Rated current (In) 250A - Switching capacity / short circuit rating SCCR 25kA (600Vac) - Thermal-Magnetic (adjustable) trip unit
Brand
SKU
LGS4250FAW
Please add this item to cart to request a quote.
Eaton Cutler-Hammer - Series G
Description
Molded/Moulded Case Circuit Breaker (MCCB) - Eaton (Series G) - LG-Frame) - 4 poles (4P3d) - Rated current (In) 250A - Switching capacity / short circuit rating SCCR 25kA (600Vac) - Thermal-Magnetic (adjustable) trip unit
Specifications
Primary brand
Eaton
Secondary brand
Cutler-Hammer
Main function
Moulded Case Circuit Breaker (MCCB)
Product series / family name
Series G
Sub-range name
LG-Frame
Network frequency
50/60 Hz
Functions
Molded/Moulded Case Circuit Breaker (MCCB)
Rated current
250A
Trip current rating
250A AT
Frame current rating
630 AF
Rated impulse voltage (Uimp)
8 kV
Rated insulation voltage (Ui)
850 V
Poles
4 Pole(s)
Protected poles
3 Pole(s)
Short circuit breaking rating
85kA (240Vac)
50kA (480Vac)
25kA (600Vac)
22kA (250Vdc)
50kA (480Vac)
25kA (600Vac)
22kA (250Vdc)
Ultimate short circuit current breaking capacity (Icu)
85kA (240Vac)
50kA (415Vac)
20kA (690Vac)
22kA (250Vdc)
50kA (415Vac)
20kA (690Vac)
22kA (250Vdc)
Service short circuit current breaking capacity (Ics)
50kA (415Vac)
10kA (690Vac)
22kA (250Vdc)
10kA (690Vac)
22kA (250Vdc)
Trip unit type
Thermal-Magnetic (adjustable)
Protection functions
Thermal protection (Overload)
Magnetic protection (Short-circuit)
Magnetic protection (Short-circuit)
Net Width (mm)
183 mm
Electrical durability (with load)
8000 operations
Service short circuit current breaking capacity (Ics)
85kA (240Vac) kA
Manufacturer product status
Commercialized
Rated voltage (AC)
(NEMA) 600 V
(IEC) 690 V
(IEC) 690 V
Compliant with standard(s)
IEC
UL
CSA
CE
UL
CSA
CE
Net width (in)
7.22 in
Related Documents
Name | Last Update | Language |
---|---|---|
Eaton - Cutler-Hammer - MCCBs - Catalog.pdf | 06 Aug 2018 | English (US) |
Eaton - Cutler-Hammer - MPCBs - Leaflet.pdf | 06 Aug 2018 | English (US) |