Eaton
LCXH13A0-5A7N1
Liquid-cooled enclosed clean power Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter chassis - Eaton / Cutler-Hammer (LCX9000) - Supply voltage 710Vdc-930Vdc / Output voltage 690Vac - Rated output current 1300A (Motor output thermal current Ith) - Rated power 900kW (Optimum output power at Ith 400V; 710-930Vdc) - Chassis CH64
Brand
SKU
LCXH13A0-5A7N1
Please add this item to cart to request a quote.
Eaton - LCX9000LCXH13A0-5A7N1
Description
Liquid-cooled enclosed clean power Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter chassis - Eaton / Cutler-Hammer (LCX9000) - Supply voltage 710Vdc-930Vdc / Output voltage 690Vac - Rated output current 1300A (Motor output thermal current Ith) - Rated power 900kW (Optimum output power at Ith 400V; 710-930Vdc) - Chassis CH64
Specifications
Primary brand
Eaton
Secondary brand
Cutler-Hammer
Main function
Variable Speed / Frequency Drive (VSD/VFD) / Inverter
Product series / family name
LCX9000
Network frequency
(input) 45-66 Hz
(output) 0-320 Hz
(output) 0-320 Hz
Functions
Liquid-cooled enclosed clean power Adjustable Variable Speed / Frequency Drive (AFD/VSD/VFD) / Inverter chassis
Supply voltage (DC)
710Vdc-930Vdc
Type of network
DC input
Rated current
1300A (Motor output thermal current Ith; 710-930Vdc)
1182A (Drive output current rated cont. IL; 710-930Vdc)
867A (Drive output current rated cont. IH; 710-930Vdc)
1182A (Drive output current rated cont. IL; 710-930Vdc)
867A (Drive output current rated cont. IH; 710-930Vdc)
Rated active power (kW)
900kW (Optimum output power at Ith 400V; 710-930Vdc)
1200kW (Optimum output power at Ith 500V; 710-930Vdc)
1200kW (Optimum output power at Ith 500V; 710-930Vdc)
Protection functions
Overvoltage
Undervoltage
Ground Fault
Mains Supervision
Motor Phase Supervision
Unit Overtemperature
Overcurrent
Motor Overload
Motor Stall
Motor Underload
Short-Circuit
Undervoltage
Ground Fault
Mains Supervision
Motor Phase Supervision
Unit Overtemperature
Overcurrent
Motor Overload
Motor Stall
Motor Underload
Short-Circuit
Net Height (mm)
924 mm
Net Width (mm)
746 mm
Net Depth (mm)
390 mm
Operating mode
Frequency control (V/f)
Open loop; Sensorless vector control
Closed loop; Frequency control
Closed loop; Vector control
Open loop; Sensorless vector control
Closed loop; Frequency control
Closed loop; Vector control
Digital inputs
6 x digital inputs (Positive or negative logic; 18-24V DC)
Digital outputs
1 x digital output (Open collector)
2 x digital outputs (SPDT Single Pole Double Throw contact type)
2 x digital outputs (SPDT Single Pole Double Throw contact type)
Analog inputs
1 x analog input (0-10V DC)
1 x analog input (0-20mA / 4-20mA)
1 x analog input (0-20mA / 4-20mA)
Analog outputs
1 x analog output (0-20mA / 4-20mA)
Ambient air temperature for operation
-10...+50 °C
Ambient air temperature for storage
-40...+70 °C
Manufacturer product status
Commercialized
Rated voltage (AC)
690 V
Compliant with standard(s)
CE marked
IEC 721-3-3
EN 50178
EN 60068-2-6
EN 60068-2-27
EN 60204-1
UL
cUL
FI
GOST R
IEC 61800-5
IEC 721-3-3
EN 50178
EN 60068-2-6
EN 60068-2-27
EN 60204-1
UL
cUL
FI
GOST R
IEC 61800-5
Related Documents
Name | Last Update | Language |
---|---|---|
Eaton - NFX9000 MVX9000 SLX9000 HVX9000 IntelliPass - Catalogue.pdf | 23 Jun 2020 | English (US) |